Ex d
How it works
The enclosure is designed to withstand the pressure of an explosion of the reference gas mixture inside it (overpressure test). All joints between enclosure parts are made as flameproof joints with a controlled maximum gap and minimum flame-path length. When an explosion occurs inside, the expanding hot gases must pass through these narrow, long gaps, where they lose heat and are cooled below the temperature capable of igniting the external atmosphere. The gap parameters are matched to the gas group (IIA/IIB/IIC) based on the Maximum Experimental Safe Gap (MESG). Cables and conductors enter through certified Ex d cable glands (barrier glands where required) so that the flameproof integrity is not compromised.
Problem solved
How to safely operate electrical and mechanical equipment that may produce sparks, arcs or hot surfaces in an atmosphere containing flammable gases or vapours, without allowing an ignition source inside the equipment to ignite that atmosphere.
Components
The enclosure body designed to withstand, without permanent deformation or loss of integrity, the pressure of an explosion of a mixture formed inside it.
Flanged, threaded or cylindrical joints with a strictly defined maximum gap and minimum length through which post-explosion gases must pass.
Certified cable and conductor entries (barrier glands where required) that preserve the flameproof integrity of the enclosure.
Hyperparameters (configurable axes)
The gas/vapour class the enclosure is certified for, linked to the MESG. IIC (e.g. hydrogen, acetylene) is the most demanding.
The permissible flameproof-joint gap selected for the gas group based on the Maximum Experimental Safe Gap.
The minimum joint length through which post-explosion gases pass; a longer path cools and quenches the flame more effectively.
The pressure the enclosure is verified against in the overpressure test for the given mixture.